![Omron SYSMAC C200H Скачать руководство пользователя страница 276](http://html1.mh-extra.com/html/omron/sysmac-c200h/sysmac-c200h_operation-manual_742423276.webp)
266
POWER and RUN indicators will be lit and the ALARM/ERROR indicator will
be flashing. The RUN output will be ON.
Error and message
FAL no.
Probable cause
Possible correction
FAL error
SYS FAIL FAL**
01 to 99
FAL(06) has been executed
in program. Check the FAL
number to determine
conditions that would cause
execution (set by user).
Correct according to cause
indicated by FAL number
(set by user).
Cycle time overrun
CYCLE TIME OVER
F8
Watchdog timer has
exceeded 100 ms.
Program cycle time is
longer than recommended.
Reduce cycle time if
possible.
I/O table verification error
I/O VER ERR
E7
Unit has been removed
making I/O table incorrect.
Use I/O Table Verify
Operation to check I/O table
and either connect dummy
Units or register the I/O
table again.
RMTE I/O ERR
Remote I/O error
*
Remote I/O
Master Unit number
B0 or B1
Error occurred in
transmissions between
Remote I/O Units.
Check transmission line
between PC and Master
and between Remote I/O
Units.
SPECIAL UNIT ERR
Special I/O error
D0
Error has occurred in PC
Link Unit, Remote I/O
Master Unit, between a
Host, SYSMAC LINK, or
SYSMAC NET Link Unit
and the CPU, or in refresh
between Special I/O Unit
and the CPU.
Determine the unit number
of the unit which caused the
error (AR 00), correct the
error, and toggle the
appropriate Restart Bit in
AR 01 or SR 252. If the unit
does not restart, replace it.
Battery error
BATT LOW
F7
Backup battery is missing or
its voltage has dropped.
Check battery and replace if
necessary.
The following error messages appear for errors that occur after program exe-
cution has been started. PC operation and program execution will stop and
all outputs from the PC will be turned OFF when any of the following errors
occur. No CPU indicators will be lit for the power interruption error. For all
Fatal Operating Errors
Error Messages
Section 8-4
Содержание SYSMAC C200H
Страница 1: ...OPERATION MANUAL C200H CPU01 E 03 E 11 E SYSMAC Programmable Controllers Cat No W130 E1 05 ...
Страница 2: ...C200H Programmable Controllers CPU01 E 03 E 11 E Operation Manual Revised June 2003 ...
Страница 3: ...iv ...
Страница 5: ...vi ...
Страница 8: ...TABLE OF CONTENTS ix Glossary 345 Index 363 Revision History 369 ...
Страница 342: ...336 Programmer Program Date Page Word Contents Notes Word Contents Notes Data Storage ...
Страница 374: ...Cat No W130 E1 05 C200H Programmable Controllers CPU01 E 03 E 11 E OPERATION MANUAL ...