7-25
D
RUN Command (Register 0001 Hex)
Bit No.
Function
0
RUN command (1: RUN)
1
Forward/Reverse (1: Reverse)
2
External fault (External fault EF0)
3
Fault reset (1: Fault reset)
4
Multi-function input 1 (1: ON)
5
Multi-function input 2 (1: ON)
6
Multi-function input 3 (1: ON)
7
Multi-function input 4 (1: ON)
8
Multi-function input 5 (1: ON)
9
Multi-function input 6 (1: ON)
10
Multi-function input 7 (1: ON)
11 to 15
Not used
Note
There is an OR relationship between input from the control terminals and input
through communications. Therefore, if multi-function inputs of this register are
set to forward/stop and reverse/stop, it is possible to execute the RUN command
through the multi-function inputs. These settings are not, however, recom-
mended because these settings establish two command lines.
D
Inverter Output (Register 0009 Hex)
Bit No.
Function
0
Multi-function contact output (1: ON)
1
Multi-function output 1 (1: ON)
2
Multi-function output 2 (1: ON)
3 to 15
Not used
Note
The settings will be enabled if multi-function outputs 1 through 3 in n057 through
n059 are set to 18 for communications output. Then the corresponding output ter-
minal will be turned ON and OFF through communications.
H
Broadcast Message with Slave Address: 00 (00 Hex)
Write
Register No.
(Hex)
Function
Description
0000
Not used
---
0001
RUN command
Refer to the table below.
0002
Frequency reference
Set the frequency reference based on the
maximum frequency as 30,000.
0003 to 000F
Not used
---
Note 1.
Data can be written to registers 0001 and 0002 only.
Communications
Chapter 7
Содержание SYSDRIVE 3G3MV A2002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Страница 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Страница 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 69: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 296: ...9 11 D 3G3MV PFI1040 E Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 298: ...9 13 D 3G3MV PFI2030 E Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 299: ...9 14 D 3G3MV PFI2050 E Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 301: ...9 16 D 3G3MV PRS3030V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 311: ...Chapter 10 List of Parameters 10...
Страница 342: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 348: ...Appendix A Standard Models...