7-4
Note
Communications data after the above conversion is hexadecimal.
For example, if the frequency is 60 Hz and the unit of setting is 0.01 Hz, the con-
verted value is obtained as follows:
60/0.01 = 6000 = 1770 Hex
H
Slave Address (n153)
·
Set this parameter to the Slave address (Slave unit number) for communications.
·
If more than one Inverter is connected as a Slave, make sure that there will be no Slave
address duplication.
n153
RS-422/485 Communica-
tions Slave Address
Register
0199
Hex
Changes during
operation
No
Setting
range
00 to 32
Unit of
setting
1
Default setting
00
Set Values
Value
Description
00
Only receives broadcast messages from the Master (see note)
01 to 32
Slave address
Note
Address 00 is for broadcast purposes only. Do not set the Slave to this address,
otherwise the Slave will not communicate.
H
Communications Baud Rate and Parity Selection (n154 and
n155)
·
Set the baud rate and parity according to the communications conditions of the Master.
n154
RS-422/485 Baud Rate
Selection
Register
019A
Hex
Changes during
operation
No
Setting
range
0 to 3
Unit of
setting
1
Default setting
2
Set Values
Value
Description
0
2,400 bps
1
4,800 bps
2
9,600 bps
3
19,200 bps
Communications
Chapter 7
Содержание SYSDRIVE 3G3MV A2002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Страница 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Страница 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 69: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 296: ...9 11 D 3G3MV PFI1040 E Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 298: ...9 13 D 3G3MV PFI2030 E Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 299: ...9 14 D 3G3MV PFI2050 E Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 301: ...9 16 D 3G3MV PRS3030V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 311: ...Chapter 10 List of Parameters 10...
Страница 342: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 348: ...Appendix A Standard Models...