6-7
Deceleration
The Inverter decelerates normally and is not in energy-saving control.
Power
consumption
Load rate: 100%
Load rate: 50%
Motor voltage
As shown in the graph, the voltage to
operate the motor most efficiently
varies with the motor load condition.
The Inverter in energy-saving control
adjusts the output voltage by using
the ideal calculated value so that the
actual output power will be minimum.
6-2-2 Performing Energy-saving Settings
n139
Energy-saving Control
Selection
Register
018B
Hex
Changes during
operation
No
Setting
range
0, 1
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Energy-saving control disabled
1
Energy-saving control enabled
Note 1.
Set n139 to 1 to enable energy-saving control.
Note 2.
Energy-saving control is enabled within a frequency range from 15 to 120 Hz
and disabled if the frequency exceeds 120 Hz.
n158
Motor Code
Register
019E
Hex
Changes during
operation
No
Setting
range
0 to 70
Unit of
setting
1
Default setting
See
note
Note
The default setting varies with the capacity of the Inverter model.
Set Values
·
The motor code is used for automatically setting the energy-saving constant in n140.
·
By setting the motor code, the value in n140 (energy-saving control coefficient K2) will
change automatically. To adjust energy-saving control coefficient K2, set the motor
code in advance.
Advanced Operation
Chapter 6
Содержание SYSDRIVE 3G3MV A2002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Страница 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Страница 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 69: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 296: ...9 11 D 3G3MV PFI1040 E Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 298: ...9 13 D 3G3MV PFI2030 E Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 299: ...9 14 D 3G3MV PFI2050 E Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 301: ...9 16 D 3G3MV PRS3030V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 311: ...Chapter 10 List of Parameters 10...
Страница 342: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 348: ...Appendix A Standard Models...