8-24
8-2-9 Controller or AM Radio Receives Noise when
Inverter is Started
·
Noise derives from Inverter switching.
Take the following actions to prevent noise.
S
Lower the carrier frequency of the Inverter in n080.
The number of internal switching times is reduced, so noise can be reduced to
some extent.
S
Install an Input Noise Filter.
Install an Input Noise Filter on the power input area of the Inverter.
S
Install an Output Noise Filter.
Install an Output Noise Filter on the output area of the Inverter.
S
Use metal tubing.
Electric waves can be shielded by metal. Therefore, enclose the Inverter with a
metal tube.
8-2-10 Ground Fault Interrupter is Actuated when
Inverter is Started
·
Leakage current flows through the Inverter.
The Inverter performs internal switching. Therefore, a leakage current flows through
the Inverter. This leakage current may actuate the ground fault interrupter, shutting
the power OFF.
Use a ground fault interrupter with a high leakage-current detection value (sensitivity
amperage of 200 mA or more, operating time of 0.1 s or more) or one with high-fre-
quency countermeasures for Inverter use.
Reducing the carrier frequency value in n080 is also effective.
In addition, remember that a leakage current increases in proportion to the cable
length. Normally, approximately 5 mA of leakage current is generated for each meter
of cable.
Maintenance Operations
Chapter 8
Содержание SYSDRIVE 3G3MV A2002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Страница 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Страница 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 69: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 296: ...9 11 D 3G3MV PFI1040 E Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 298: ...9 13 D 3G3MV PFI2030 E Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 299: ...9 14 D 3G3MV PFI2050 E Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 301: ...9 16 D 3G3MV PRS3030V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 311: ...Chapter 10 List of Parameters 10...
Страница 342: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 348: ...Appendix A Standard Models...