6-19
·
This parameter adjusts the feedback value so that the input level of the input device,
such as a sensor, will coincide with the input level of the target value.
For example, if the target value of 1,000 rpm is input as 10 V and the Feedback Value
Adjustment Gain should be set to 2.
n130
Proportional (P) Gain
Register
0182
Hex
Changes during
operation
Yes
Setting
range
0.0 to 25.0
Unit of
setting
0.1
Default setting
1.0
n131
Integral (I) Time
Register
0182
Hex
Changes during
operation
Yes
Setting
range
0.0 to 360.0 (s)
Unit of
setting
0.1 s
Default setting
1.0
n132
Derivative (D) Time
Register
0182
Hex
Changes during
operation
Yes
Setting
range
0.0 to 2.50 (s)
Unit of
setting
0.01 s
Default setting
0.00
Set Values
·
While the mechanical load is in actual operation, adjust the values so that the best
response will be returned from the load. Refer to
6-3-7 PID Adjustments
.
·
If n130 (proportional gain) is set to 0.0, PID control will be disabled. Not only propor-
tional control but also all PID control will be disabled.
·
If n131 (integral time) is set to 0.0, integral control will be disabled.
·
If n132 (derivative time) is set to 0.0, derivative control will be disabled.
n133
PID Offset Adjustment
Register
0185
Hex
Changes during
operation
Yes
Setting
range
--100 to 100 (%)
Unit of
setting
1%
Default setting
0
Set Values
·
This parameter is for the offset adjustment of all PID control.
·
Adjust the parameter so that the output frequency of the Inverter will be 0 when the
target value and feedback value are both set to 0.
n134
Integral (I) Upper Limit
Register
0186
Hex
Changes during
operation
Yes
Setting
range
0 to 100 (%)
Unit of
setting
1%
Default setting
100
Set Values
·
Set this parameter to the upper limit of integral control output.
Advanced Operation
Chapter 6
Содержание SYSDRIVE 3G3MV A2002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Страница 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Страница 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 69: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 296: ...9 11 D 3G3MV PFI1040 E Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 298: ...9 13 D 3G3MV PFI2030 E Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 299: ...9 14 D 3G3MV PFI2050 E Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 301: ...9 16 D 3G3MV PRS3030V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 311: ...Chapter 10 List of Parameters 10...
Страница 342: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 348: ...Appendix A Standard Models...