6-20
·
Set the value in percentage based on the maximum frequency as 100%.
·
The integral upper limit is set so that the output frequency will not be excessively high
when the deviation is large.
n135
PID Primary Delay Time
Register
0187
Hex
Changes during
operation
Yes
Setting
range
0.0 to 10.0 (s)
Unit of
setting
0.1 s
Default setting
0.0
Set Values
·
Set this parameter to the primary delay time constant for the frequency reference after
PID control.
·
Normally, the default setting does not need to be changed.
·
If load is a mechanical one with high viscous friction or low rigidity, the load may reso-
nate. If that happens, set a value larger than the resonant frequency of the load so that
the load will not resonate, even though the response will be slower.
n136
Feedback Loss Detection
Selection
Register
0188
Hex
Changes during
operation
No
Setting
range
0 to 2
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Feedback loss detection disabled
1
Feedback loss detection enabled (Nonfatal error: FbL warning)
2
Feedback loss detection enabled (Fatal error: FbL error)
Note 1.
Set the method of detecting loss of the feedback as a detected value for PID
control.
Note 2.
If the detection level set in n137 or lower is detected for the set time in n138, the
result will be determined as feedback loss.
n137
Feedback Loss Detection
Level
Register
0189
Hex
Changes during
operation
No
Setting
range
0 to 100 (%)
Unit of
setting
1%
Default setting
0
n138
Feedback Loss Detection
Time
Register
018A
Hex
Changes during
operation
No
Setting
range
0.0 to 25.5 (s)
Unit of
setting
0.1 s
Default setting
1.0
Set Values
·
These parameters are reference values for detecting loss of feedback for PID control.
Advanced Operation
Chapter 6
Содержание SYSDRIVE 3G3MV A2002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Страница 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Страница 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 69: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 296: ...9 11 D 3G3MV PFI1040 E Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 298: ...9 13 D 3G3MV PFI2030 E Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 299: ...9 14 D 3G3MV PFI2050 E Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 301: ...9 16 D 3G3MV PRS3030V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 311: ...Chapter 10 List of Parameters 10...
Страница 342: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 348: ...Appendix A Standard Models...