10-25
Param-
eter
No.
Ref-
er-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of
set-
ting
Set-
ting
range
Description
Name
Regis-
ter No.
n139
018B
Energy-sav-
ing control
selection
Select the energy-saving control func-
tion.
0: Disabled
1: Enabled
Note
This parameter is enabled in V/f
control mode only.
0, 1
1
0
No
6-7
n140
018C
Energy-sav-
ing control
coefficient K2
Set the coefficient for the primary
level of energy-saving control.
Note
The constant automatically
changes according to the motor
code in n158. Make fine adjust-
ments of the contact if neces-
sary after setting the motor
code in n158.
0.0 to
6.550
0.1
Varies
with the
capac-
ity
No
6-8
n141
018D
Energy-sav-
ing voltage
lower limit at
60-Hz output
These parameters prevent the output
voltage of the Inverter from dropping
excessively so that the motor will not
stall or come to a stop at the primary
level of energy-saving control.
Set the lower limit of output voltage in
0 to
120
1%
50
No
6-9
n142
018E
Energy-sav-
ing voltage
upper limit at
6-Hz output
Set the lower limit of output voltage in
percentage at each frequency based
on the rated motor voltage as 100%.
Note
Normally, the default settings
do not need to be changed.
0 to 25 1%
12
No
6-9
n143
018F
Power aver-
aging time
Set the time required to calculate the
average of power used in energy-sav-
ing control.
Power averaging time (ms) = Set
value x 24 (ms)
Note
Normally, the default setting
does not need to be changed.
1 to
200
1 (24
ms)
1
No
6-9
n144
0190
Probe opera-
tion voltage
limit
Set the range of voltage control for
the secondary level of energy-saving
control.
Set the parameter in percentage
based on the rated motor voltage as
100%.
Note
No probe operation is available
with the parameter set to 0.
0 to
100
1%
0
No
6-10
n145
0191
Probe opera-
tion control
voltage step
at 100%
Set the range of probe operation volt-
age in percentage based on the rated
motor voltage as 100%.
Note
Normally, the default setting
0.1 to
10.0
0.1%
0.5
No
6-11
n146
0192
Probe opera-
tion control
voltage step
at 5%
Note
Normally, the default setting
does not need to be changed.
0.1 to
10.0
0.1%
0.2
No
6-11
n147
---
Not used
---
---
---
---
---
---
n148
---
Not used
---
---
---
---
---
---
List of Parameters
Chapter 10
Содержание SYSDRIVE 3G3MV A2002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Страница 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Страница 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 69: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 296: ...9 11 D 3G3MV PFI1040 E Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 298: ...9 13 D 3G3MV PFI2030 E Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 299: ...9 14 D 3G3MV PFI2050 E Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 301: ...9 16 D 3G3MV PRS3030V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 311: ...Chapter 10 List of Parameters 10...
Страница 342: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 348: ...Appendix A Standard Models...