6-51
Set Values
·
For the input open-phase detection level (n166), set the main-circuit DC voltage fluc-
tuation level for detecting an input open phase. Set the level as a percentage, as fol-
lows:
200-V-class Inverters:
Take 400 V as 100%.
400-V-class Inverters:
Take 800 V as 100%.
·
For the input open-phase detection time (n167), set the time (in seconds) for detecting
an input open phase.
Note 1.
The following values are recommended for detecting an input open phase:
n166 = 7 (%); n167 = 10 (s)
Note 2.
If either n166 or n167 is set to 0, the input open-phase detection function will be
disabled.
6-10-11
Output Open-phase Detection (n168, n169)
·
The output open-phase detection function is provided for 5.5-kW and 7.5-kW Inverters
only.
·
This function detects the occurrence of an output terminal open phase. The detection
is performed at the current flowing at each output phase.
·
If the current in any of the Inverter output phases becomes less than the output open-
phase detection level (n168) and persists at this level for longer than the output open-
phase detection time (n169), an output open-phase fault (LF) will be detected
.
n168
Output Open-phase
Detection Level
Register
01A8
Hex
Changes during
operation
No
Setting
range
0 to 100
Unit of
setting
1 %
Default setting
0
n169
Output Open-phase
Detection Time
Register
01A9
Hex
Changes during
operation
No
Setting
range
0.0 to 2.0
Unit of
setting
0.1 s
Default setting
0.0
Set Values
·
For the output open-phase detection level (n168), set the current for detecting an out-
put open phase. Make the setting as a percentage, taking the Inverter’s rated output
current as 100%.
·
For the output open-phase detection time (n169), set the time in seconds for detecting
an output open phase.
Note 1.
The following values are recommended for detecting an output open phase:
n168 = 5 (%); n169 = 0.2 (s)
Advanced Operation
Chapter 6
Содержание SYSDRIVE 3G3MV A2002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Страница 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Страница 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 69: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 296: ...9 11 D 3G3MV PFI1040 E Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 298: ...9 13 D 3G3MV PFI2030 E Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 299: ...9 14 D 3G3MV PFI2050 E Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 301: ...9 16 D 3G3MV PRS3030V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 311: ...Chapter 10 List of Parameters 10...
Страница 342: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 348: ...Appendix A Standard Models...