6-4
n109
Torque Compensation Limit Register
016D
Hex
Changes during
operation
No
Setting
range
0 to 250 (%)
Unit of
setting
1%
Default setting
150
Note 1.
The Inverter in torque compensation control limits the torque at a current 1.5
times larger than the set value.
Note 2.
This parameter is enabled only when the Inverter is in vector control.
H
Adjusting the Torque and Response through the V/f Pattern
(n011 through n017)
·
The Inverter in vector control uses the V/f pattern as the reference value of the output
voltage. Therefore, by adjusting the V/f pattern the output torque and response are
adjusted.
·
If the application requires high torque, adjust the V/f pattern so that the output voltage
at the required frequency will be high. Furthermore, energy-saving effects can be
expected by decreasing the output voltage values in the frequency ranges where high
torque is not required.
n011
Maximum Frequency
(FMAX)
Register
010B
Hex
Changes during
operation
No
Setting
range
50.0 to 400.0 (Hz)
Unit of
setting
0.1 Hz
Default setting
60.0
n012
Maximum Voltage (VMAX)
Register
010C
Hex
Changes during
operation
No
Setting
range
0.1 to 255.0 (0.1 to 510.0) (V)
Unit of
setting
0.1 V
Default setting
200.0
(400.0)
n013
Maximum Voltage
Frequency (FA)
Register
010D
Hex
Changes during
operation
No
Setting
range
0.2 to 400.0 (Hz)
Unit of
setting
0.1 Hz
Default setting
60.0
n014
Middle Output Frequency
(FB)
Register
010E
Hex
Changes during
operation
No
Setting
range
0.1 to 399.9 (Hz)
Unit of
setting
0.1 Hz
Default setting
1.5
n015
Middle Output Frequency
Voltage (VC)
Register
010F
Hex
Changes during
operation
No
Setting
range
0.1 to 255.0 (0.1 to 510.0) (V)
Unit of
setting
0.1 V
Default setting
11.0
(22.0)
Advanced Operation
Chapter 6
Содержание SYSDRIVE 3G3MV A2002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Страница 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Страница 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 69: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 296: ...9 11 D 3G3MV PFI1040 E Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 298: ...9 13 D 3G3MV PFI2030 E Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 299: ...9 14 D 3G3MV PFI2050 E Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 301: ...9 16 D 3G3MV PRS3030V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 311: ...Chapter 10 List of Parameters 10...
Страница 342: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 348: ...Appendix A Standard Models...