8-18
8-2 Troubleshooting
Due to parameter setting errors, faulty wiring, and so on, the Inverter and
motor may not operate as expected when the system is started up. If that
should occur, use this section as a reference and apply the appropriate
measures.
Refer to
8-1 Protective and Diagnostic Functions
, if the contents of the fault
are displayed,
8-2-1 Parameters Fail Set
H
The display does not change when the Increment or
Decrement Key is pressed.
·
Parameter write-prohibit is input.
This occurs when n001 for parameter write-prohibit selection/parameter initializa-
tion is set to 0. Set n001 to an appropriate value according to the parameter to be set.
·
The Inverter is operating.
There are some parameters that cannot be set during operation. Refer to the list of
parameters. Turn the Inverter OFF and then make the settings.
H
“OP
j
”
is displayed.
A parameter setting error has occurred. Refer to
8-1-2 Warning Detection (Nonfatal
Error)
and make the necessary corrections.
H
Nothing is displayed on the Digital Operator or “OPR” is
displayed.
A connection error has occurred in the Digital Operator.
Turn OFF the Inverter and dismount the Digital Operator. After checking that the con-
nector is free of any foreign material remount the Digital Operator.
8-2-2 Motor Fails to Operate
H
The motor does not operate with input through the control
circuit terminals even though the frequency reference is
correct.
·
The operation method setting is incorrect.
If parameter n003 for operation mode selection is not set to 1 to enable the control
circuit terminals, the RUN command cannot be executed through the control circuit
terminals.
Maintenance Operations
Chapter 8
Содержание SYSDRIVE 3G3MV A2002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Страница 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Страница 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 69: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 296: ...9 11 D 3G3MV PFI1040 E Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 298: ...9 13 D 3G3MV PFI2030 E Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 299: ...9 14 D 3G3MV PFI2050 E Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 301: ...9 16 D 3G3MV PRS3030V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 311: ...Chapter 10 List of Parameters 10...
Страница 342: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 348: ...Appendix A Standard Models...