6-44
n082
Number of Fault Retries
Register
0152
Hex
Changes during
operation
No
Setting
range
0 to 10
Unit of
setting
1
Default setting
0
Set Values
·
Set the number of fault retries required.
·
The count of fault retries will be cleared in any of the following cases.
The Inverter is normal for 10 minutes continuously after the latest fault retry was
made.
Power supply to the Inverter is interrupted.
A fault reset is input.
6-10-6 Frequency Jump Function (n083 to n086)
·
The frequency jump function prevents the Inverter from generating frequencies that
make the mechanical system resonate.
·
The frequency jump function can be used effectively to set three dead bands of a fre-
quency reference.
n083
Jump Frequency 1
Register
0153
Hex
Changes during
operation
No
Setting
range
0.00 to 400.0 (Hz)
Unit of
setting
0.01 Hz
Default setting
0.00
n084
Jump Frequency 2
Register
0154
Hex
Changes during
operation
No
Setting
range
0.00 to 400.0 (Hz)
Unit of
setting
0.01 Hz
Default setting
0.00
n085
Jump Frequency 3
Register
0155
Hex
Changes during
operation
No
Setting
range
0.00 to 400.0 (Hz)
Unit of
setting
0.01 Hz
Default setting
0.00
n086
Jump Width
Register
0156
Hex
Changes during
operation
No
Setting
range
0.00 to 25.50 (Hz)
Unit of
setting
0.01 Hz
Default setting
0.00
Set Values
·
Set n083 through n085 for jump frequencies 1 through 3 to the central values of jump-
ing frequencies.
Advanced Operation
Chapter 6
Содержание SYSDRIVE 3G3MV A2002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Страница 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Страница 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 69: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 296: ...9 11 D 3G3MV PFI1040 E Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 298: ...9 13 D 3G3MV PFI2030 E Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 299: ...9 14 D 3G3MV PFI2050 E Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 301: ...9 16 D 3G3MV PRS3030V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 311: ...Chapter 10 List of Parameters 10...
Страница 342: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 348: ...Appendix A Standard Models...