6-43
n081
Momentary Power
Interruption Compensation
Register
0151
Hex
Changes during
operation
No
Setting
range
0 to 2
Unit of
setting
1
Default setting
0
Set Values
Value
Description
0
Disabled. (An undervoltage fault will be detected when there is momentary
power interruption for 15 ms or more.)
1
The Inverter will continue operating if power is restored within 0.5 s.
(see note 1)
2
The Inverter will restart when power is restored. (see note 2)
Note 1.
By setting n081 to 1, the Inverter will detect UV warning, turn OFF the output,
and wait for power restoration for 0.5 s if a momentary power interruption
occurs. If the power recovers within 0.5 s, the Inverter will restart after speed
searching. If the momentary power interruption continues more than 0.5 s, the
Inverter will detect UV1.
Note 2.
By setting n081 to 2, the Inverter will detect UV warning, turn OFF the output,
and wait for power restoration if a momentary power interruption occurs. When
the power recovers, the Inverter will restart after speed searching.
6-10-5 Fault Retry (n082)
Caution
The Inverter may break if the fault retry function is used.
If the Inverter breaks, take the following measures:
Be sure to install a no-fuse breaker (NFB).
Provide the Inverter and peripheral machines with a sequence so
that the machines will stop operating when the Inverter has an
operational fault.
·
The fault retry function automatically resets and restarts the Inverter in the case the
Inverter has an overvoltage fault or an overcurrent fault during operation.
·
In the case of any other fault, the protective function operates instantly and the fault
retry function does not operate.
·
This function is to be used only if the user does not want to interrupt the mechanical
system, even if this function may damage the Inverter.
·
Set a multi-function output (n057 to n059) to the following so that the fault retry signal
will be output.
Set value: 14 for fault retries
Advanced Operation
Chapter 6
Содержание SYSDRIVE 3G3MV A2002
Страница 1: ...USER S MANUAL SYSDRIVE 3G3MV Multi function Compact Inverter Cat No I527 E2 02...
Страница 15: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1 3 New Features 1...
Страница 24: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Страница 69: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Parameter Copy and Verify Function 3...
Страница 89: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Страница 286: ...Chapter 9 Specifications 9 1 Inverter Specifications 9 2 Option Specifications 9...
Страница 296: ...9 11 D 3G3MV PFI1040 E Three 5 dia holes Four M4 holes for Inverter mounting use Specifications Chapter 9...
Страница 298: ...9 13 D 3G3MV PFI2030 E Four M4 holes for Inverter mounting use Three 5 dia holes Specifications Chapter 9...
Страница 299: ...9 14 D 3G3MV PFI2050 E Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 301: ...9 16 D 3G3MV PRS3030V Four M5 holes for Inverter mounting use Three 6 dia holes Specifications Chapter 9...
Страница 311: ...Chapter 10 List of Parameters 10...
Страница 342: ...Chapter 11 Using the Inverter for a Motor 11...
Страница 348: ...Appendix A Standard Models...