the
metrocluster config-replication resync-status show
command.
6. Reestablish any SnapMirror or SnapVault configurations.
Step 7: Return the failed part to NetApp
Return the failed part to NetApp, as described in the RMA instructions shipped with the kit. See the
Swap out a fan - FAS8200
To swap out a fan module without interrupting service, you must perform a specific
sequence of tasks.
You must replace the fan module within two minutes of removing it from the chassis. System
airflow is disrupted and the controller module or modules shut down after two minutes to avoid
overheating.
1. If you are not already grounded, properly ground yourself.
2. Remove the bezel (if necessary) with two hands, by grasping the openings on each side of the bezel, and
then pulling it toward you until the bezel releases from the ball studs on the chassis frame.
3. Identify the fan module that you must replace by checking the console error messages and looking at the
Attention LED on each fan module.
4. Press down the release latch on the fan module cam handle, and then pull the cam handle downward.
The fan module moves a little bit away from the chassis.
Cam handle
Fan module
377