P199e
Available in D8x/D16x V5.6 and later.
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
Options 1e-5e OFF - Serial data
options disabled.
notes
The RS232 Serial data is output at 9600
baud, 8 data bits, no parity, 1 stop bit.
SeRIAl OUTPUT OPTIONS
D8x and D16x V5.6 and later have the option for two way serial data communications
via the onboard RS232 SeRIAl port. Alarm and system messages can be sent and
keypad/status request data can be received. This allows high level interfacing with
various external devices/controllers/dataloggers and other.
Messages are in ASCII format. Due to space constraints, the full protocol is not printed
in this manual but is available on request.
PROGRAMMING SeQUeNCe:
P199e 1e–5e
toggles the option ON and OFF
1e on: Send address. the address is the last digit of acc no.2 (P73e).
2e on: Send time Stamp.
3e on: Send alarms.
4e on: Send Warnings.
5e on: Send access events.
6e on: Send Zone Seal State. (D8x/D16x v6 and later.)
Option No.
Description
Default
P199e
1e
Send Address
OFF
2e
Send Time Stamp
OFF
3e
Send Alarms
OFF
4e
Send Warnings
OFF
5e
Send Access events
OFF
6e
Zone Seal State (D8x/D16x V6 and later)
OFF
7e
[not used]
OFF
8e
[not used]
OFF
75
NeSS D8X / D16X DelUXe CONTROl PANel – INSTAllATION MANUAl
P r o g r A m m i n g