P145e
AUx1 timer
Available in D8x/D16x V6 and later.
ProgrAm moDe leVel
Installer mode or NessComms V5.3
or later.
FACtory DeFAUlt
20 sec.
relAteD oPtions
P141e 8e
Sets the length of pulse time for the AUX1 output when the P141e 8e option is selected.
Select 1 to 99 seconds.
TO PROGRAM
Press P145e (The existing Pulse Time will be displayed).
Press [NeW TIMe] e (The new Pulse Time will be displayed).
P141e 1e – 8e
enHAnCeD AUx1 oUtPUt oPtions
Available in D8x/D16x V6 and later.
ProgrAm moDe leVel
Installer mode or NessComms V5.3
or later.
FACtory DeFAUlt
All off.
notes
Any or all options may be selected on.
The P141e enhanced AUX1 options work along with P121e and AutoTimers to provide
multiple choices of events and alarms to control AUX1.
TO PROGRAM
1. Press
P141e.
2. Press
1e ... 8e
to turn an option on. Multiple options can be selected.
P141e 1e
AreA 1 ArmeD to AUx1
Turns on AUX1 while Area 1 is armed.
P141e 2e
AreA 2 ArmeD to AUx1
Turns on AUX1 while Area 2 is armed.
P141e 3e
Home ArmeD to AUx1
Turns on AUX1 while armed in Home mode.
P141e 4e
keyPAD toggle AUx1
When this option is on,
AUX1 is turned ON or PUlSeD with the keypress 11* (* = left hand STAR button).
AUX1 is turned OFF with the keypress 11# (# = Right hand STAR button).
P141e 5e
telePHone remote Control oF AUx1
notes
Remote operation by telephone
procedure as detailed in the user and
installation manuals must be followed
before access is allowed. This includes
entering a valid user code.
relAteD oPtions
P90e 5e, enable remote Aux control.
P141e 8e Pulse AUX1.
When this option is on and you have connected to the panel by telephone remote control:
AUX1 is turned ON or PUlSeD with the telephone keypress 11*
AUX1 is turned OFF with the telephone keypress 11#
FeeDbACk tones HeArD by PHone:
3 BeePS: The AUX has been turned ON or is already ON.
1 BeeP: The AUX has been turned OFF or is already OFF.
1 lONG BeeP: error. Remote AUX operation by telephone is not enabled.
P141e 8e
PUlse AUx1
relAteD oPtions
P145e, AUX1 Pulse Time.
This option converts the P121e 1e and the P141e 1e, 2e, 3e, 4e, 5e options into a pulsed
AUX1 output.
AUX1 is pulsed on for the time set in P145e.
Option No.
Description
Default
Note
P145e
AUX1 TIMeR
20 sec
1 to 99 seconds
AUx1
OUTPUT OPTIONS
59
NeSS D8X / D16X DelUXe CONTROl PANel – INSTAllATION MANUAl