DisAble DiAller
This option disables the dialler even if telephone numbers and other dialler options are
programmed.
Up/download or remote telephone access remain enabled.
PROGRAMMING SeQUeNCe:
P86e 1e
turns the option ON
on: Dialler disabled
P86e 1e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
Off: dialler enabled.
notes
This option is useful for temporary
disabling of the dialler without affecting
other dialler options.
ContACt iD FormAt
This option enables the reporting of alarms to a Central station via telephone numbers
1 & 2 using Contact ID format.
PROGRAMMING SeQUeNCe:
P86e 2e
turns the option ON
on: Contact iD format enabled
P86e 2e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
ON: Contact ID format enabled.
rePort nAme
ssss
Q
xyZ
gg
CCC
sUFFix
Zone 1– Zone 16 Alarm
ssss 18
q
130
aa
001–016
k
Duress
ssss 18
1
121
01
030
k
Keyswitch Panic
ssss 18
1
120
01
031
k
Keypad Panic
ssss 18
1
120
01
032
k
Radio Key Panic
ssss 18
1
120
01
1dd
k
Medical Alarm
ssss 18
1
100
01
033
k
Fire
ssss 18
1
110
01
034
k
exit Install mode
ssss 18
1
306
01
035
k
external Tamper
ssss 18
q
137
01
040
k
Internal Tamper
ssss 18
q
137
01
041
k
Keypad Tamper
ssss 18
q
137
01
042
k
Radio Sensor Supervision
ssss 18
q
381
01
4zz
k
Radio Sensor Tamper
ssss 18
q
383
01
2zz
k
Radio Sensor low Battery
ssss 18
q
384
01
3zz
k
Mains Fail
ssss 18
q
301
01
050
k
Panel Battery Fail
ssss 18
q
309
01
051
k
Open (Disarm)
ssss 18
1
402
aa
0dd
k
Force Open (Cancel)
ssss 18
1
406
aa
0dd
k
Close (Arm)
ssss 18
3
402
aa
0dd
k
Closing extended
ssss 18
3
464
aa
0dd
k
Test Report
ssss 18
1
602
01
063
k
Zone 1-16 Manual exclude
ssss 18
q
573
aa
001-016
k
Zone 1-16 Auto exclude
ssss 18
q
380
aa
001-016
k
CONTACT ID RePORTS TABle
The panel reports alarms to the Central
Station using Contact ID dialler format.
The message format is fixed as shown
in the Contact ID Codes Table.
the message takes the form of:
ssss
Account Number
Q
event qualifier
1=New event or Open
3=Restore or Close
xyZ
Alarm type
gg
Group or Area designation
CCC
Alarm number
dd=User ID (1 to 56)
zz = Zone ID (1 to 16)
aa = 01 Area 1
aa = 02 Area 2
aa = 01 Monitor area
aa = 00 24 Hr Area
K = Checksum
(0 to 0f hex)
SPeCIAl ARMING/DISARMING RePORTS By USeR
Option No.
Description
Default
P86e
1e
Disable Dialler
OFF
2e
CONTACT ID FORMAT
ON
3e
[not used]
OFF
4e
Audible VOICe Format
OFF
5e
[not used]
OFF
6e
Contact ID + VOICe Format
OFF
rePort nAme
User iD
Arm/Disarm by Keyswitch
57
Shortcut Arm
58
Arm/Disarm by AutoTimer 1
91
Arm/Disarm by AutoTimer 2
92
Arm/Disarm by AutoTimer 3
93
rePort nAme
User iD
Arm/Disarm by AutoTimer 4
94
Arm/Disarm by AutoTimer 5
95
Arm/Disarm by AutoTimer 6
96
Arm/Disarm by AutoTimer 7
97
Arm/Disarm by AutoTimer 8
98
43
NeSS D8X / D16X DelUXe CONTROl PANel – INSTAllATION MANUAl
P r o g r A m m i n g