P340 - P345e
reAltime CloCk ProgrAmming
Available in D8x/D16x V6 and later.
ProgrAm moDe leVel
User Mode, Installer mode or
NessComms V5.3 or later.
FACtory DeFAUlt
none
notes
Real Time Clock memory is regularly
saved to non-volatile memory and is
retained on power down.
you should always check the clock
settings on power up and adjust the
time and date if necessary.
These options are used to program the time and date into the Realtime Clock (RTC).
TO PROGRAM
1. Press
P340e - P345e
2. Press
[new value] e
LCD keypads - the programmed time is displayed one digit at a time.
Navigator keypad - the programmed time is displayed on screen
P340e
Real Time Clock minutes. enter a value between 00 and 59. Default 00 minutes.
P341e
Real Time Clock Hours. enter a value between 00 and 23. Default 00 hours.
P342e
Real Time Clock Day of the month. enter a value between 01 and 31. Default 01,
(1st day of the month). ensure that the setting does not exceed the days in the current
month. The panel does not cross-check this setting.
P343e
Real Time Clock Month. enter a value between 01 and 12. Default 01, (January).
P344e
Real Time Clock year. enter a value between 00 and 63. (2000–2063). Default 09,
(2009).
P345e
Real Time Clock Day Of The Week. This value is calculated from the date. No
programming is necessary. Use this option only to view the Day Of The Week. (1=Sunday).
Default 1, (Sunday).
P390
AUtotime WArning PerioD
Available in D8x/D16x V6 and later.
ProgrAm moDe leVel
Installer mode or NessComms V5.3
or later.
FACtory DeFAUlt
5 minutes
notes
This option sets the warning period
for all AutoTimers.
relAteD oPtions
P353e 6e AutoTimer1, keypad beeps
P358e 6e AutoTimer2, keypad beeps
P363e 6e AutoTimer3, keypad beeps
P368e 6e AutoTimer4, keypad beeps
P373e 6e AutoTimer5, keypad beeps
P378e 6e AutoTimer6, keypad beeps
P383e 6e AutoTimer7, keypad beeps
P388e 6e AutoTimer8, keypad beeps
This option enables a keypad beep to warn that an AutoTime action is due to begin.
Set the minutes for the start of the warning period.
The Keypad Beeps option for the required timer/s must also be enabled.
TO PROGRAM
1. Press
P390e
2. Press
[new value] e
The allowed range is 1 to 99 minutes.
LCD keypads - the programmed time is displayed one digit at a time.
Navigator keypad - the programmed time is displayed on screen
P392e 1e
enAble AUtotime User CoDes
Available in D8x/D16x V6 and later.
ProgrAm moDe leVel
Installer mode or NessComms V5.3
or later.
FACtory DeFAUlt
1e OFF
Toggle the current setting for the eNABlING or DISABlING of USeR Codes as set by the
AutoTIMeRS.
If the USeR codes are currently DISABleD but the current AutoTIMe period means that
they should be eNABleD then use this option.
TO PROGRAM
1. Press
P392e.
2. Press
1e
to turn the option ON or OFF.
Turn the option ON to enable User codes.
Option No.
Description
Default Note
P340e
ReAl TIMe ClOCK SeT
minUtes
00
00–59 minutes
P341e
ReAl TIMe ClOCK SeT
HoUrs
00
00–23 hours
(00=midnight)
P342e
ReAl TIMe ClOCK SeT
DAy
01
01–31 days
P343e
ReAl TIMe ClOCK SeT
montH
01
01–12 months
P344e
ReAl TIMe ClOCK SeT
yeAr
09
00–63
(2000–2063)
P345e
ReAl TIMe ClOCK VIeW
DAy oF Week
1
1–7
(1=Sunday, 7=Saturday)
70
NeSS D8X / D16X DelUXe CONTROl PANel – INSTAllATION MANUAl
70
AUtomAtion