Zone sUPerVision Alerts – siren oUtPUt
Setting this option turns the Siren output ON when a SUPeRVISeD ZONe alert occurs.
The Siren output will remain ON for the duration of the AlARM TIMe (Set by Option
P29e).
PROGRAMMING SeQUeNCe:
P66e 4e
toggles the option ON and OFF
oFF: Supervision Siren output disabled
on: Supervision Siren output enabled
P66e 4e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
OFF: Supervision Siren output disabled.
relAteD oPtions
P65e Supervised Zones.
Zone sUPerVision Alerts – reset oUtPUt
Setting this option turns the Reset output ON when a SUPeRVISeD ZONe alert occurs.
The Reset output will remain ON for the duration of the AlARM TIMe (Set by Option
P29e).
PROGRAMMING SeQUeNCe:
P66e 1e
toggles the option ON and OFF
oFF: Supervision reset output disabled
on: Supervision reset output enabled
P66e 1e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
OFF: Supervision Reset output
disabled.
relAteD oPtions
P65e Supervised Zones.
Zone sUPerVision Alerts – strobe oUtPUt
Setting this option turns the Strobe output ON when a SUPeRVISeD ZONe alert
occurs. The Strobe output will remain ON until the panel is disarmed.
PROGRAMMING SeQUeNCe:
P66e 2e
toggles the option ON and OFF
oFF: Supervision Strobe output disabled
on: Supervision Strobe output enabled
P66e 2e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
OFF: Supervision Strobe output
disabled.
relAteD oPtions
P65e Supervised Zones.
Zone sUPerVision Alerts – keyPAD sonAlert
Setting this option turns the Keypad Sonalert ON when a SUPeRVISeD ZONe alert
occurs. The Keypad Sonalert remains ON until
any
keypad key is pressed.
Also, turning this option ON makes all Supervision outputs delayed by one minute.
PROGRAMMING SeQUeNCe:
P66e 3e
toggles the option ON and OFF
oFF: Supervision Keypad Sonalert disabled and all Supervision outputs trigger instantly
on: Supervision Keypad Sonalert enabled and all Supervision outputs are delayed by 1 minute
P66e 3e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
OFF: Supervision Keypad Sonalert
disabled.
notes
• When this option is turned ON, it
delays the operation of all other selected
Supervision outputs by one minute.
relAteD oPtions
P65e Supervised Zones.
Option No.
Description
Default
P66e
1e
Zone Supervision alarm to ReSeT output
OFF
2e
Zone Supervision alarm to STROBe
OFF
3e
Zone Supervision alarm to SONAleRT
OFF
4e
Zone Supervision alarm to SIReN
OFF
5e
enable WIReD ZONe supervision
OFF
6e
OFF
7e
Zone Supervision speedup x 6
OFF
8e
Zone Supervision speedup x10
OFF
32