P60e 2e, 3e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
No keyswitch enabled.
P60e 2e, 3e off.
notes
The keyswitch:
a/ Always Arms Area1 only.
b/ Does not arm Area2.
c/ Can disarm Area2 if option P120e 8e is
enabled.
• The keyswitch input will only operate if
the eOl resistor value of 2k2 is selected
for zone inputs. See P129e, page 68.
relAteD oPtions
P120e 1e latched Keyswitch.
P120e 4e Keyswitch Disarms only.
P120e 5e Keyswitch Arms only.
P120e 8e Keyswitch disarm Area2.
P129e eOl Resistor value
keysWitCH oPerAtion
An externally fitted, normally open momentary Keyswitch can be used to Arm, Disarm
or arm the Home mode.
The keyswitch is wired to zone 8 (zone 8 is then no longer available as a normal alarm
input, but is still available for use as a Radio Zone).
PROGRAMMING SeQUeNCe:
P60e 2e or 3e
toggles the option ON and OFF
2e & 3e oFF: no keyswitch operation. Zone 8 is a normal alarm input.
2e on: Keyswitch cycles between Home and Disarm.
3e on: Keyswitch cycles between arm and Disarm.
2e & 3e on: Keyswitch cycles between arm, Home and Disarm.
P60e 2e is on
P60e 3e is on
P60e 2e is on
P60e 3e is on
ARMED
ARMED
MONITOR
MONITOR
DISARM
DISARM
DISARM
KeySWITCH WIRING
If P60e 2e or 3e are enabled, use a momentary action keyswitch with normally open
contacts. A momentary closed circuit across the resistor will toggle panels modes.
Open circuit the resistor to trigger Panic if required. (Panic on this input is disabled if
P120e 1e is enabled).
If P120e 1e is enabled, use a latching keyswitch. When the resistor is sealed, panel is
disarmed. If the resistor is unsealed, (either by open circuit or short circuit), the panel
will arm Area1, (Area2 will be ignored).
ARMED
ARMED
MONITOR
MONITOR
DISARM
DISARM
DISARM
P120e 1e is on
Momentary
Keyswitch
Momentary
Keyswitch
Momentary
Keyswitch
latching
Keyswitch
entry beePs
The sonalert will beep during entry Delay.
PROGRAMMING SeQUeNCe:
P60e 1e
toggles the option ON and OFF
oFF: entry Beeps oFF
on: entry Beeps on
P60e 1e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
entry Beeps ON.
relAteD oPtions
P69e 7e Arm exit Beeps.
P69e 8e Home exit Beeps.
KeySWITCH WIRING.
A momentary or latching keyswitch
can be wired as shown.
Option No.
Description
Default
P60e
1e
entry Beeps
ON
2e
Keyswitch Home Monitor/Disarm
OFF
3e
Keyswitch Arm/Disarm
OFF
4e
Tamper Siren lockout
ON
5e
Duress to ReSeT output
OFF
6e
Auto exclude zones
ON
7e
Auto keypad display off
OFF
8e
Delayed Aux3, Aux4 outputs
OFF
24