DAy Zones
Day Zones operate when the panel is fully disarmed, i.e. when Area 1, Area 2 and
Home are all off. When alarmed, these zones will activate their assigned outputs
instantly.
The outputs mapped to the Day Zone will turn on while the zone is unsealed. Turn
P64e 2e on, to limit Day Zone alarms to 2 seconds.
The Temporary Day Zones feature allows day mode to be easily enabled/disabled and
day zones added/removed by the user from any keypad.
PROGRAMMING SeQUeNCe:
P53e [Zone no]e
toggles the options ON and OFF
[Zone no] oFF: the zone is not a Day zone
[Zone no] on: the zone is a Day zone
P53e
ProgrAm moDe leVel
Installer, Remote by PC
FACtory DeFAUlt
all OFF: No Day zones
relAteD oPtions
P63e 5e-8e
Day zone output mapping.
P64e 2e
Brief Day Mode alarm.
P120e 6e
Smart Beeps for Home and Day
zones.
TyPICAl USeS FOR DAy ZONeS: Instant
alert when a delivery door is opened,
doorway alert for a shop.
24hr Zones
24hr Zones operate at all times regardless of the mode of panel operation, i.e. Armed,
Disarmed or Home Monitor. When alarmed, these zones will activate assigned outputs
immediately. To reset those alarms a valid user code must be entered.
Selecting a zone as 24hr will override any other zone type setting such as Instant,
Delayed or Handover. 24hr zones are independent of Area operation. All other zone
types must be assigned to at least one Area to become active.
PROGRAMMING SeQUeNCe:
P52e [Zone no]e
toggles the options ON and OFF
[Zone no] oFF: the zone is not a 24hr zone
[Zone no] on: the zone is a 24hr zone
P52e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
All OFF: No 24hr zones.
notes
• The Tamper input is always a 24hr
zone.
• For silent 24hr zones, deselect the zone/
s from options P54e-P57e (Reset, Strobe,
Sonalert & Siren).
• To change a 24hr zone to any other
zone type, the zone must also be re-
assigned to an AReA (P45e or P46e).
Home Zones
Home zones allow you to Arm selected zones while others are ignored. Typically used
for perimeter zones such as windows and doors while you are at home.
For example: upstairs zones are Disarmed while downstairs zones are Armed in Home
mode.
PROGRAMMING SeQUeNCe:
P51e [Zone no]e
toggles the options ON and OFF
P51e [Zone no]e oFF: the zone is not a Home zone
P51e [Zone no]e on: the zone is a Home zone
P51e
ProgrAm moDe leVel
Installer mode or NessComms.
FACtory DeFAUlt
all OFF: No Home zones.
notes
By default, all Home zones have entry
Delay2, see P64e 3e. If this option is off
Home zones have normal entry delay
attributes set by options P40e–P42e.
relAteD oPtions
P63e
Home Mode output mapping.
P64e 1e
Brief Home alarm.
P64e 3e
Home zones have entry Delay2.
P69e 3e
Quiet Home siren.
P69e 5e
Radio Key ON or OFF button
arms Home Mode.
P120e 2e
Home arm chirps by radio key.
P120e 3e
Radio Key AUX button arms
Home mode.
P120e 6e
Smart Beeps for Home and Day
zones.
NOTe: Zones selected to Report Zone Alarms (P74e) will by default report alarms in
Home Mode, (if the dialler is enabled).
The Brief Home Alarm option P64e 1e, when enabled, prevents Home alarms from
reporting.
P47e, P48e, P49e, P50e
Assigning User CoDes to AreAs
Options P201e–P256e are now used for assigning user codes to areas.
(experienced users can still use options P47e–P50e for this function, but only up to
user code 15).
See page 14, 15 programming User
Codes.
See page 20 for information on TeMPORARy DAy ZONeS.
See page 20 for Home operation.
21
NeSS D8X / D16X DelUXe CONTROl PANel – INSTAllATION MANUAl
P r o g r A m m i n g