PROFINET
User manual 58185_TREE M4/6-TX PN IP20_hdb_en_10
95/103
PROFINET Factory Reset
The second option is the PROFINET Factory Reset which resets all PROFI-
NET-relevant configurations.
The PROFINET Factory Reset can be carried out as described in:
a | Chapter 11.3 "PROFINET menu",
b | In the external diagnostic tool (e.g. PRONETA).
The settings are reset to:
Tab. 12-6: PROFINET Factory Reset
The following settings are maintained after the PROFINET Factory Reset:
Port modes
NTP settings
Device name and description
Contact
Location
Parameter
There are 2 parameters:
RSTP
Default Value: "1" in the ParameterRecordDataItem IDT_RSTPON
Temperature warning
Default Value: "1" in the ParameterRecordDataItem IDT_RSTPON
Standard functions:
Monitoring of the ports
Display of error messages, if necessary
Alarms and diagnostics
The modules send diagnostic information.
Diagnostics types:
Alarms according to the PROFINET specification V2.33,
Alarms when the temperature limits are exceeded.
Temperature warning limits:
Lower temperature limit: 0 °C
Upper temperature limit: 70 °C
Property
Options
Value
RSTP
Enabled/disabled
Status is maintained
MRP
Enabled/disabled
Disabled
LLDP
Device name
Enabled
PROFINET
Device name
Valid IP address
Is deleted:
Empty string
IP address
IP address/net mask
0.0.0.0
Configuration of all
network ports
Automatic
Automatically with monitoring
100 Mbits/s, full duplex
100 Mbits/s half-duplex
10 Mbits/s, full duplex
10 Mbits/s half-duplex
Settings are maintained
IP configuration
Static
DHCP
Static
DCP
Enabled/disabled
Enabled