Technical data
User manual 58185_TREE M4/6-TX PN IP20_hdb_en_10
36/103
5.2.5
Mechanical data
5.2.6
Environmental characteristics
Climatic conditions
NOTE
Temperature rating of the cable to be connected to the field wiring terminals:
≤
60 °C
Electrical safety
5.2.7
Tests and classification
Mechanical tests
Parameter
Conditions
Value
Housing material
Polyamide PA 6.6
Flammability class
UL94
V-0
Dimensions
L x W x D
111 x 45 x 99 mm
Weight
170 g
Fastening
According to DIN EN 60715
Mounting rail TH35
Installation position
Perpendicular to
mounting rail
Parameters
Conditions
Value
Operating temperature
range
0 … +60 °C
Storage temperature range
-40 … +85 °C
Air humidity
(Operation and storage)
Non-condensing
5 ... 95 %
Operating altitude
Above mean sea level
≤
3000 m
Parameters
Conditions
Value
Degree of protection
According to EN 60529
IP20
MTTF
>10 years
Parameters
Conditions
Value
Shock test
IEC 60068-2-27
Shock 15 g,
11 ms duration
6 shocks per axis (18
shocks)
Vibration resistance
IEC 60068-2-6, crit. 3
Vibration:
10 cycles per axis
(30 cycles),
1 octave/min
5-9 Hz constant am-
plitude, 3.5 mm
9-150 Hz; constant
acceleration 1 g
Free fall
EN 61131-2
1 m