3
Control Menu
The following sections detail:
•
Temperature Curve, page 15
•
Humidity Treatment, page 24
•
CO2 Treatment, page 25
•
Min/Max Level, page 26
•
•
Control Mode, page 34
•
System Parameters, page 34
•
Ammonia Treatment, page 35
3.1
Temperature Curve
This screen sets the temperature targets according to the bird/pig age.
1. In
Install > Analog Sensors
(refer to Analog Sensors, page 109), designate the required number
of sensors as temperature sensors. When using more than one sensor, Farm Premiumbegins
treatments based on the average.
2. If required, go to
Service > Temperature Calibration
, calibrate the sensors (refer to Temperature
Calibration, page 94).
3. In
Install > Temperature Definition
(refer to Temperature Definition, page 114), assign specific
sensors brood setups, heater zones, and devices. If a zone does not have an assigned sensors,
calculations are based on the current average temperature.
4. In
Control > Temperature Curve
, define the required target temperature curve
o
Set up to 20 lines, 999 growth days. When a curve is not required (for example when
growing layers), enter temperatures in the first line only.
o
Define:
Day: Set the growth day. You can program negative growth days up to -2 for pre-
warming. To enter a negative growth day, type the day number followed by the ±
key.
CONTROL
1. TEMPERATURE CURVE
2. HUMIDITY TREATMENT
3. CO2 TREATMENT
4. MIN/MAX LEVEL
5. STATIC PRESSURE
6. CONTROL MODE
7. SYSTEM PARAMETERS
8. AMMONIA TREATMENT
TEMPERATURE CURVE
Day
Target Heat Tunnel
Alarm
Low High
T.Hi
1
2
3
7
15
21
28
35
42
48
89.0
89.0
87.0
84.0
82.0
79.0
76.0
72.0
70.0
68.0
89.0
89.0
87.0
83.0
81.0
78.0
74.0
70.0
68.0
66.0
100.0
99.0
97.0
91.0
89.0
86.0
81.0
77.0
75.0
73.0
84.0
84.0
82.0
80.0
78.0
75.0
71.0
67.0
63.0
60.0
102.0
102.0
95.0
95.0
93.0
90.0
87.0
84.0
83.0
83.0
103
103
103
103
103
103
103
103
103
103