© Munters AB, 2015
91
The readings can vary from 0 to 1023. The values displayed in the 'Value' column indicate that the
analog sensor is operating or not according to the following:
•
If a very large value is shown (such as a four digit number) or a small value is shown (such as a
one digit number): sensor is not connected.
•
If the unit displays a 3-digit number, usually beginning with the digit '4: sensor is operating.
8.4
Digital Sensors
This screen displays the digital sensors states.
Define sensors in Installation > Digital Sensors.
A ‘1’ implies a shorted input, a ‘0’ an open input. The digital sensors operate with dry contact inputs such
as the Arad Water Meter, or micro-switches.
You can apply a short/open input to each channel; the response is then displayed.
NOTE:
The water meter quantities appear on the main screen or on Hot Screen 0.
8.5
Analog Output
This screen tests light dimmers, variable speed fans, and variable heaters.
1. Scroll to the required output.
2. Enter the test voltage and verify that the device is operating.
Define sensors in Installation > Analogue Output.
ANALOG IN TEST
In.
Sensor
A/Value
1
Temp. Sensor 1
470
64.0
2
Temp. Sensor 2
426
87.2
3
Temp. Sensor 3
470
85.6
4
Temp. Sensor 4
426
82.0
5
Temp. Sensor 5
470
87.0
6
<None>
7
<None>
8
<None>
9
<None>
10
<None>
DIGITAL IN TEST
In.
Sensor
State
Counter
1
Water Meter 1
1
0
2
Water Meter 2
0
0
3
Fogger Water Meter
0
0
4
AUX. Alarm
0
0
5
AUX. Alarm
0
0
6
Low Water Pressure
0
0
7
Wind Speed
0
0
8
<None>
0
0