The static pressure sensor is located inside the controller in the upper left hand corner to the left of the
power supply.
•
Refer to Static Pressure, page 31.
9.5
Light Sensor Calibration
NOTE:
Broilers/Layers mode supports this feature.
Installing a light sensor enables turning off the lights when there is sufficient outside light.
To calibrate the light sensor:
1. Go to
Install > Analog Sensors
(page 109).
2. Define one sensor as a light sensor.
3. Go to
Device > Light
(page 49).
4. Press Help, highlight Set, and press Enter.
5. Scroll down to Light Sensor Active and set to Yes.
6. Place the sensor in the required location.
7. Go to
Service > Light Sensor Calibration
.
8. When the outside light is bright enough, press Enter
STATIC PRESSURE CALIBRATION
A/D Counts:
110
Disconnect air hoses from the Farm
Premium to zero the pressure
Then Press ENTER to calibrate
STATIC PRESSURE CALIBRATION
A/D Counts:
110
GOOD CALIBRATION
Press MENU to exit