Levels of Ventilation, page 38
•
Variable Speed Fan Levels, page 41
•
Vent & Curtain Levels, page 41
•
Stir Fan Levels, page 43
•
Stir Fan Program, page 44
•
•
•
•
Water & Feed, page 51
•
Extra Systems, page 54
•
Emergency Setting, page 54
•
Water on Demand, page 56
•
Natural Program, page 58
4.1
Levels of Ventilation
The Precision Ventilation table provides up to 30 ventilation levels controlling both variable fans and
relay-controlled fans. To program this table, start with the minimum ventilation used in the first level and
increase ventilation gradually. A reasonable rule of thumb is to increase the airflow about 25% at each
level. Increases in airflow up to 50% work satisfactorily with factory default settings.
1. Do one or both:
o
In
Install > Relay Outlet
(refer to page 107) define at least one relay as a Tunnel Fan or
Exhaust Fan.
o
In
Install > Analog Output
(refer to page 110) define one function as Tunnel Fan or
Exhaust Fan.
2. In
Device Setting > Levels of Ventilation
configure the parameters as required.
3. Configure the Help Set parameters as required.
DEVICE SETTING
1. LEVELS OF VENTILATION
2. SPEED FAN LEVELS
3. VENT & CURTAIN LEVELS
4. STIR FAN LEVELS
5. STIR FAN PROGRAM
6. COOL PAD
7. FOGGERS
8. LIGHT
9. WATER & FEED
10. EXTRA SYSTEMS
11. EMERGENCY SETTING
12. WATER ON DEMAND
13. NATURAL PROGRAM
LEVELS OF VENTILATION
No
Diff
On
Exhaust
Tunnel
Deg. Sec
1
2
3
1
2 3
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
30
45
60
80
120
160
200
250
100
120
150
180
0
150
0
0
0.0.
Air Capacity: 300
-Continuous
Chill Range:
--- -Cycle
-Rotate
Tunnel Level: T