Shortage Start Day: Define on what day shortage alarms begin. This parameter prevents false
alarms caused by young birds low water usage. Default: 0 (meaning alarms function normally
throughout the growth cycle).
Bird Scales Alarms
•
Allow Bird Scale Alarms From/To: Set time frame for which the controller begins and ends
generating alarms for the bird scale.
Auxiliary Alarms
•
Assign auxiliary alarms in the Install menu. Note that digital sensors, auxiliary alarm input with
related relay must always match their relay status.
•
Related Relay For Aux Alarm 1/2/3/4: Relay for Auxiliary Alarm 1/2/3/4.
•
AUX. Alarm Delay (sec): Separate from the Global Alarm Delay. If there is a dry contact, the
alarm is sent after the defined AUX. Alarm Delay.
Circuit Breaker Alarm
•
Temperature for Circuit Breaker Alarm: Set circuit breaker alarm temperature.
CO2 Sensor Alarm
•
CO2 High Level: Set the maximum allowed CO2 level above which an alarm is sent. The
alarm ceases when the CO2 drops below this level. If the user acknowledges the alarm, the
alarm messages temporarily cease (for the reminder time).
Humidity Sensor Alarm
•
Humidity High Level Alarm: Set the maximum allowed humidity level above which an alarm is
sent. The alarm ceases when the humidity drops below this level. If the user acknowledges the
alarm, the alarm messages temporarily cease (for the reminder time).
Ammonia Alarm
•
Ammonia High Level: Set the ammonia level at which an alarm is sent.
Secondary Alarms
•
Enable Secondary Alarms: Refer to Prioritizing Alarms, page 72.
Potentiometer Alarm
5.5.2
P
RIORITIZING
A
LARMS
Farm Premium 5.16 enables prioritizing alarms. When enabled:
•
ventilation-related alarms are defined as critical. The main alarm relay will transmit these
alarms to the device wired to the relay (for example, a dialer).
•
non-ventilation alarms are defined as non-critical. A secondary relay will transmit alarms to
another device (for example, an ELS).
To prioritize alarms:
1. Go to Install > Relay Layout.
2. Define a relay as Alarm (N.C.).
3. Go to Manage > Alarm Setting > Help
4. Enable Advanced Alarms.
5. Go to Manage > Alarm Setting.