9.14
Wind Direction Calibration
Use this screen to calibrate a wind direction sensor.
Define an analog sensor as wind direction.
9.15
WOD Calibration
Define an analog sensor as WOD.
1. In
Installation > Setup
, set the Length Unit.
o
Metric = Bar
o
Non Metric = PSI
2. In
Service > WOD Calibration
:
a. Enter the first voltage and check pressure data points.
b. Repeat for second data points.
3. Set the Help Definitions (optional)
9.15.1
WOD
C
ALIBRATION
H
ELP
|
S
ET
D
EFINITIONS
This parameter reduces the water pressure a user-defined factor.
1. In
Install > Setup
, define the Pressure unit.
2. In
Service > WOD Calibration
> Help, define the reduction factor. Water pressure is reduced
by 1/50 (bar or PSI). The factor is accurate to two decimal points.
9.16
Ammonia Calibration
Define an analog sensor as ammonia sensor.
WIND DIRECTION CALIBRATION
Direction
Calibration
Wind Direction 6
14.50
WATER ON DEMAND CALIBRATION
Volt
Pressure - PSI
WOD 1st Calib. 2.50
14.50
WOD 2nd Calib. 7.50
43.50
READ ME
Enter output voltage for first point.
Enter water meter measure pressure.
Repeat this for the second point.
SYSTEM PARAMETERS
WATER ON DEMAND
Pressure Reducer Factor
50.00