Minimum Ventilation
•
Static Pressure at Low Temperature: Set desired static pressure for low outside temperature
conditions. Be sure that there is proper airflow at this setting.
•
Static Pressure at High Temperature: Set desired static pressure for high temperature
conditions. Normally this pressure is lower to obtain a larger air inlet opening.
NOTE:
Controller interpolates between the LOW and HIGH Temperature. If Static Pressure exists,
then it is controlled by the outside temperature sensor, otherwise the average temperature.
•
Low Static Pressure Alarm: Set alarm for low static pressure. If you disable it by setting zero,
the Farm Premium warns you and enters a record in the Table of Events.
•
High Static Pressure Alarm: Set alarm for high static pressure.
•
Static Pressure Band: Set desired band for the target pressure.
Tunnel Ventilation
•
Target Static Pressure: Set required static pressure for Tunnel Ventilation Mode.
•
Low Static Pressure Alarm: Set alarm for low static pressure.
•
High Static Pressure Alarm: Set alarm for high static pressure.
•
Static Pressure Band: Set required band for pressure in tunnel ventilation mode.
Attic
•
Target Static Pressure: Set required static pressure when in attic mode.
•
Static Pressure Band: Set required band for attic ventilation mode.
3.6.1
D
ISABLING THE
S
TATIC
P
RESSURE
S
ENSOR
To disable the static pressure sensor:
1. Go to
Installation > Setup
.
2. Set the Static Pressure Unit to None.
The main screen stops:
o
displaying the pressure
o
displaying High Pressure and Pressure Sensor Failure alarms
NOTE:
If either of these alarms were active before disabling the sensor, the main screen continues to
display the alarms. Reset the alarms one time to cease the display.
STATIC PRESSURE
Minimum Ventilation
S.Press. At Low Temperature
S.Press. At High Temperature
Low Static Pressure Alarm
High Static Pressure Alarm
Static Pressure Band
Tunnel Ventilation
Target Static Pressure
Low Static Pressure Alarm
High Static Pressure Alarm
Static Pressure Band
Attic
Target Static Pressure
0.120
0.080
0.010
0.150
0.040
0.080
0.010
0.150
0.040