© Munters AB, 2015
22
o
interpolation inside the band
•
There is 0% voltage when the target temperature is reached.
•
Define.
o
Difference Above Heat to Stop Heater: Differential from target temperature at which
the heater runs at minimal input
o
High Difference Below Heat: High Difference Below Heat: Temperature at which the
heater begins to operate at maximum output.
3.1.5
V
ARIABLE
F
LOOR
H
EATER
|
S
ET
D
EFINITIONS
Farm Premium Controllers enable configuring up to two variable floor heaters. The output of the heaters
changes as the temperature increases or decreases.
Install at least one analog output card.
To configure the variable floor heaters:
1. In
Installation > Analog Output
configure:
a. up to two analog outputs as variable heaters
b. the minimum and maximum voltage output for each heater
SYSTEM PARAMETERS
RADIANT HEATERS
Rad. Low –Diff from Heat Set
Rad. High –Diff (Below Low Set)
Radiant Ignition Time (sec)
VARIABLE HEATER
Low Diff Below Heat Tmp.
High Diff Below Heat Tmp.
VARIABLE FLOOR HEATER
Low Diff Below Heat Tmp.
High Diff Below Heat Tmp.
0.0
1.0
30
0.5
4.5
0.5
4.5