82
6.8
Test
This section is a real time table to show the statuses of all scales connected to the controller.
1. In
Scale > Scale Layout
(refer to page 77), select the required scale types.
2. In
Scale > Test
, test the scales as required.
Make sure that all statuses are O.K. If any of them show a different status, the scale is not installed
properly. Unused positions can also show O.K.
6.9
Calibration
This menu calibrates the scales and silos connected to the controller.
1. In
Scale > Scale Layout
(refer to page 77), select the required scale types.
2. In
Scale > Calibration
, calibrate the scales.
CAUTION
Do not use scales while calibrating.
6.9.1
S
CALE
C
ALIBRATION
1. Follow instructions on the bottom section of the screen.
2. Wait until the progress bar displayed shows 100%.
3. Place a known weight on the scale and enter its weight.
4. Wait until the calibration progress bar reaches 100%.
5. Ensure “Good Calibration.”
TEST
- 1 -
- 2 -
- 3 -
- 4 -
Type
A/D
Weight
Status
Scale-1
2024
0.222
O.K.
Scale 2
2010
35.768
O.K.
Scale 3
1891
0.000
O.K.
Scale 4
1893
0.000
O.K.