8 Operation
Maschinenfabrik Reinhausen GmbH 2020
187
3587317/21 EN
TAPCON
®
For the tap stagger parallel operation method, you have to set the following
parameters:
Parameter
Master
Follower
Yes
Tap stagger
Follower
Yes
Yes
1
Master/follower current blocking
[
Off
Off
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Error if no communication present
[
Yes
Behavior if no communication
present [
Independent regulation, auto blocking or power
factor
Parallel operation error delay time
[
Yes
Table 63: Parameter
1
If there are several followers in your system, only the follower with the high-
est CAN bus address participates in the tap stagger function.
Special operating situations
▪ If you switch the master from auto mode to manual mode during the tap
stagger parallel operation method, the follower immediately switches to
the master's current tap position. To avoid this, you must activate manual
mode on both the master and follower simultaneously.
▪ If you change the parallel operation method of the master from tap stag-
ger to master, the tap stagger level is first reduced to 0 before parallel op-
eration according to the tap synchronization method becomes active.