14 Overview of parameters
Maschinenfabrik Reinhausen GmbH 2020
301
3587317/21 EN
TAPCON
®
14 Overview of parameters
This section contains an overview of the relevant menus and parameters.
The availability of individual parameters varies depending on your device
function.
Parameter
Setting range
Factory setting
Current setting
Settings > Parameters > General
Language
2
In accordance with order
IP address
0.0.0.0...255.255.255.255
192.0.1.230
Subnet mask
0.0.0.0...255.255.255.255
255.255.255.0
Gateway address
0.0.0.0...255.255.255.255
0.0.0.0
SSL encryption
On; Off
Off
Commissioning wizard
Yes; No
Yes
Measured value display
Primary values; Secondary
values
Primary values
Transformer name
-
Transformer
Remote behavior
HW, SCADA, HW+SCADA HW+SCADA
Settings > Parameters > Control
Desired value 1
49.0...140.0 V
100.0 V
Desired value 2 (optional)
Desired value 3 (optional)
Desired value 4 (optional)
Desired value 5 (optional)
Select the desired value (op-
tional)
Desired value 1..3 or de-
sired value 1...5
Desired value 1
Desired value specification maxi-
mum (optional)
49.0...140.0 V
120.0 V
Desired value specification mini-
mum (optional)
49.0...140.0 V
80.0 V
Desired value step width (op-
tional)
0.1 to 10.0 V
1.0 V
Activate TDSC (optional)
On, Off
Off
TDSC Umax (optional)
49.0...140.0 V
105.0 V
TDSC Umin (optional)
49.0...140.0 V
95.0 V
TDSC U0 (optional)
49.0...140.0 V
100.0 V
TDSC Pmax (optional)
0.1...1,000.0 MW
10.0 MW
TDSC Pmin (optional)
-1,000.0...-0.1 MW
-10.0 MW
Bandwidth
0.50...9.00%
1.00%
Delay time T1
1.0...600.0 s
40.0 s