Control variable
You can use this parameter to set which control variable the device is to reg-
ulate. You can select the following options:
▪ Voltage
▪ Reactive power
Depending on your selection, the device uses the associated parameter set
for each option (desired value, bandwidth, etc.).
Standard regulation mode
You can set use this parameter to set the operating mode of the on-load tap-
changer regulation.
8.12 Voltage regulation
All of the parameters required for voltage regulation are described in this
section.
Settings
Parameters
Voltage re...ion
Name
Value
Desired value 1
100 V
Desired value 2
100 V
Desired value 3
100 V
Selecting a desired value
Desired value 1
Bandwidth
1.0 %
Delay time T1
40 s
Time response T1
Linear
Activate delay time T2
Off
Delay time T2
10 s
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
23.09.2020 09:23
Figure 104: Voltage regulation (example)
1. Go to
Settings > Parameters > On-load tap-changer regulator > Volt-
age regulation
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
8.12.1 Setting the desired value
In accordance with the order, the device is equipped with one of the follow-
ing variants for setting the desired value: