![MR TAPCON Скачать руководство пользователя страница 287](http://html.mh-extra.com/html/mr/tapcon/tapcon_operating-instructions-manual_1844346287.webp)
11 Event messages
Maschinenfabrik Reinhausen GmbH 2020
287
3587317/21 EN
TAPCON
®
No.
Name
Description
Remedy
348
Generic digital input 38
There is a signal at the generic digital in-
put 38.
-
349
Generic digital input 39
There is a signal at the generic digital in-
put 39.
-
350
Generic digital input 40
There is a signal at the generic digital in-
put 40.
-
351
Generic digital input 41
There is a signal at the generic digital in-
put 41.
-
352
Generic digital input 42
There is a signal at the generic digital in-
put 42.
-
1229
Target tap position: Mas-
ter
The master has not reached the target
tap position.
Check the parameters, function, wiring
and motor-drive unit of the master. Acti-
vate MANUAL mode and then AUTO
mode.
1230
Target tap position: Fol-
lower
The follower has not reached the target
tap position.
Check the parameters, function, wiring
and motor-drive unit of the follower. Acti-
vate MANUAL mode and then AUTO
mode.
1231
Followers on the CAN
bus > 1
Several followers are present in the par-
allel operation group.
Check the current system configuration.
1232
Limit value Pos< follower Value has reached or fallen below the
limit value for tap position Pos< follower.
Check the current operating conditions of
the transformer of the follower and the
set parameter Pos< follower.
1233
Limit value Pos> follower Value has reached or exceeded the limit
value for tap position Pos> follower.
Check the current operating conditions of
the transformer of the follower and the
set parameter Pos> follower.
Table 126: Event messages