14 Overview of parameters
Maschinenfabrik Reinhausen GmbH 2020
303
3587317/21 EN
TAPCON
®
Parameter
Setting range
Factory setting
Current setting
Settings > Parameters > Parallel operation
Activate parallel operation
Off, On
Off
Parallel operation method
Circulating reactive cur-
rent; Master; Follower; Au-
tomatic tap synchroniza-
tion; Power factor
Circulating reactive current
CAN bus address
0...16
0
Circulating reactive current sensi-
tivity
0.0...100.0%
0.0%
Circulating reactive current block-
ing limit
0.5...20.0%
20.0%
Master/follower current blocking
Off, On
Off
Maximum tap difference
1...4
1
Error, if no communication
present
No error, Error
No error
Behavior for communication fail-
ure
No error, Error
No error
Behavior, if no communication
present
Independent regulation,
auto blocking, cosφ inter-
polation
Independent regulation
Delay time par. op. error mes-
sage
1...30 s
5 s
Settings > Parameters > Retrofit TAPCON®2xx
Retrofit TAPCON® 2xx
Off, On
Off
Settings > Parameters > Voltage monitoring
U< relative/absolute
Relative, Absolute
Relative
U< [V]
40.0...160.0 V
90.0 V
U< [%]
60.0...100.0%
90.0%
U< hysteresis
0.0...10.0 V
0.0 V
U< delay time
0.5...60.0 s
0.5 s
U< behavior
Off, High-speed return U+,
Auto blocking, Auto/man-
ual blocking
Off
U<< relative/absolute
Relative, Absolute
Relative
U<< [V]
40.0...160.0 V
80.0 V
U<< [%]
60.0...100.0%
80.0%
U<< hysteresis
0.0...10.0 V
0.0 V
U<< delay time
0.5...60.0 s
0.5 s
U<< behavior
Off, High-speed return U+,
Auto blocking, Auto/man-
ual blocking
Off