8 Operation
Maschinenfabrik Reinhausen GmbH 2020
207
3587317/21 EN
TAPCON
®
Setting
Behavior
Auto blocking position-
The automatic control does not perform a tap-change
operation in the direction of a lower tap position (posi-
tion-).
You can continue to perform tap-change operations in
manual mode.
Auto blocking p
The automatic control does not perform a tap-change
operation in the direction of a higher tap position (posi-
tion+).
You can continue to perform tap-change operations in
manual mode.
Auto/manual blocking
Automatic regulation is blocked.
You
cannot
perform tap-change operations in manual
mode.
Auto/manual blocking po-
sition-
The automatic control does not perform a tap-change
operation in the direction of a lower tap position (posi-
tion-).
You
cannot
perform a tap-change operation in the di-
rection of a lower tap position (position-) in manual
mode.
Auto/manual blocking po-
The automatic control does not perform a tap-change
operation in the direction of a higher tap position (posi-
tion+).
You
cannot
perform a tap-change operation in the di-
rection of a higher tap position (p) in manual
mode.
Table 73: Behavior when an event message is issued
8.19.4 Power flow monitoring
A reversal of power flow occurs if the active power is negative. You can set
the following parameters for this:
▪ Hysteresis
▪ Delay time
▪ Behavior