![MR TAPCON Скачать руководство пользователя страница 162](http://html.mh-extra.com/html/mr/tapcon/tapcon_operating-instructions-manual_1844346162.webp)
8 Operation
Maschinenfabrik Reinhausen GmbH 2020
162
3587317/21 EN
TAPCON
®
8.14.2.1 1-phase measurement
Circuit 1-A
UI
L1
N
VT
CT
U
L1
I
L1
L
N
k
l
▪ The voltage transformer VT is connected to the phase conductor and neu-
tral conductor.
▪ The current transformer CT is looped into the phase conductor.
▪ The voltage U
L1
and current I
L1
are in phase.
▪ The voltage drop on a phase conductor is determined by the current I
L1
.
If you use this circuit, set the device as follows:
Parameter
Option
Voltage-transformer circuit
1 Ph phase voltage
Current-transformer circuit
1 Ph phase current
Phase angle correction
0°
Table 46: Circuit 1-A
Circuit 1-B
U
L1
I
L1
L1
L2
L3
N
VT
CT
U
L1
I
L1
I
L2
I
L3
U
L3
U
L2
UI
L
N
k
l
▪ The voltage transformer VT is connected to the phase conductor L1 and
the neutral conductor.
▪ The current transformer CT is looped into the phase conductor L1.
▪ The voltage U and current I are in phase.
▪ The voltage drop on a phase conductor is determined by the current I
L1
.
Содержание TAPCON
Страница 1: ...Voltage regulator TAPCON Operating Instructions 3587317 21 EN ...
Страница 333: ......