8 Operation
Maschinenfabrik Reinhausen GmbH 2020
140
3587317/21 EN
TAPCON
®
3. Press the
Accept
button to save the modified parameter.
Selecting a desired value
You can use this parameter to select the desired value used for control.
1. Go to
Settings > Parameters > Grid > Control > Select desired value
.
2. Select the desired value from the list.
3. Press the
Accept
button to save the modified parameter.
8.12.1.4 Analog setting of the desired value
With the analog setting of the desired value, the desired value for the auto-
matic voltage regulation can be variably adapted using an analog signal (e.g.
4...20 mA).
Max.
Min.
Desired value
Max.
Min.
Analog signal
Figure 105: Analog setting of the desired value
In order to configure the analog setting of the desired value, you can set the
parameters as described below.
To specify the desired value using an analog signal, you need to create a
signal at the
Desired value setting release
input. If this is not done, the de-
vice uses the set desired value 1.
Setting desired value 1
1. Go to
Settings > Parameters > Grid > Control > Desired value
.
2. Enter the desired value.
3. Press the
Accept
button to save the modified parameter.