8 Operation
Maschinenfabrik Reinhausen GmbH 2020
124
3587317/21 EN
TAPCON
®
Figure 94: Configuring IEC 60870-5-104 data points
Proceed as follows to configure the data points:
1. Go to
Settings > Data point configuration
.
2. Adjust the data points as required.
3. Press the
Accept
button to adopt the modified list of data points.
4. Restart the device to activate the modified list of data points.
8.8.8.4 Configuring Modbus data points
You can adjust the following data point properties for the Modbus control
system protocol:
Column
Description
Modifiable
Setting range
Active
You can use the checkbox to set whether the data point is
to be transferred via the control system protocol or not.
Yes
Active/inactive
Type
Data point type
No
-
Index1
Data point address
Yes
0...65,535
Index2
Optional second data point address. This is used auto-
matically for data points able to transfer values greater
than 16 bits. Please note that the Index2 address always
follows on from the Index1 address exactly.
No
-
Name
Data point designation
No
-
Table 36: Configuring Modbus data points