![MR TAPCON Скачать руководство пользователя страница 238](http://html.mh-extra.com/html/mr/tapcon/tapcon_operating-instructions-manual_1844346238.webp)
8 Operation
Maschinenfabrik Reinhausen GmbH 2020
238
3587317/21 EN
TAPCON
®
8.25.2 Configuring events
The events have the following properties:
Property
Description
Event name
Brief name of event. If you delete all of the text, the stan-
dard text is displayed.
Event description
Description of event. If you delete all of the text, the stan-
dard text is displayed.
Event troubleshooting
Instructions for troubleshooting the cause of an event. If
you delete all of the text, the standard text is displayed.
Category
▪ Error (red)
▪ Warning (yellow)
▪ Info (gray)
This setting affects the color of the
Alarm
LED and the
event symbol in the primary navigation.
Report
If you activate this option, the event is shown on the dis-
play and, if configured accordingly, issued via an output
and the control system protocol.
Save
If you activate this option, the event is stored in the event
memory.
Multi-set
(not configurable)
The event can be triggered several times without having
been deactivated in the meantime.
High active
(not configurable)
High active: The device generates a signal if the event is
pending.
Low active: The device generates a signal so long as the
event is not pending. If the event is pending, the signal is
reset.
Acknowledgeable
(not configurable)
Acknowledgeable events must be acknowledged in the
event overview so that they are no longer displayed. All
other events are automatically removed once the cause is
remedied (e.g. limit value is no longer exceeded).
Blocking
(not configurable)
If the event is active, it blocks automatic voltage regula-
tion.
Table 84: Properties of events
Содержание TAPCON
Страница 1: ...Voltage regulator TAPCON Operating Instructions 3587317 21 EN ...
Страница 333: ......