8 Operation
Maschinenfabrik Reinhausen GmbH 2020
116
3587317/21 EN
TAPCON
®
Example:
Configuration
To configure the device as a GOOSE publisher, you have to call up the vi-
sualization via a PC. You must have a parameter configurator or administra-
tor user role.
To configure the device as a GOOSE publisher, proceed as follows:
1. Go to
Settings > Export
.
Figure 87: Exporting SCADA configuration
2. Select the
SCADA configuration
option.
ð
The SCADA configuration is exported as a zip archive.
3. Unzip the zip archive and adapt the TEMPLATE.icd file to the require-
ments.
4. Go to
Settings > Import
.