6 Mounting
Maschinenfabrik Reinhausen GmbH 2020
63
3587317/21 EN
TAPCON
®
3. As an alternative to step 2, connect the COM 2 interface (D-Sub 9-pole) to
the control system (SCADA) in accordance with the connection diagram.
Figure 47: Serial SCADA connection via COM 2 interface
6.6.7 Wiring the UI assembly
You must fuse the voltage measurement circuit in accordance with the con-
ductor cross section used. You can use the following fuse types:
Miniature circuit breaker
Safety fuse
Standard
IEC 60947-2
IEC 60269
Rated voltage
400 V (L-L) or 230 V (L-N)
Rated current
30 mA...16 A
Characteristics
B, C, K or Z
Fast-acting, medium-act-
ing or delayed-acting
Rated switching capacity
50 kA
For installation in accordance with IEC 61010-2-30
CAT II: 10 kA
Table 15: Permissible fuse types