8 Operation
Maschinenfabrik Reinhausen GmbH 2020
103
3587317/21 EN
TAPCON
®
Device ID
You can use this parameter to assign a device ID to the device in order that
it can be identified in the IEC 61850 network.
Access point
You can use this parameter to assign a name to the access point in the IEC
61850 network.
Edition
You can use this parameter to switch between edition 1 and edition 2 of the
IEC 61850 control system protocol.
8.8.1.1 Downloading an ICD file
You can download the ICD file from the device via the Import/Export Man-
ager [
Section 8.28, Page 251]. To do this, you have to establish an Ether-
net connection between the device and your PC.
8.8.1.2 Importing CID/SCD file (optional)
Note the following definitions for importing a CID file or SCD file.
Only the following elements may differ between the imported IED and the
exported IED from the TEMPLATE.icd.
▪ DataSet elements can be created in each LN
▪ ReportControl elements can be created in the LN containing the associ-
ated DataSet
▪ IP address (if this is not present, the preset one is used)
▪ Subnet mask (if this is not present, the preset one is used)
▪ Gateway IP address (if this is not present, the preset one is used)
▪ Name of IED (IED name)
▪ Name of AccessPoint (AccessPoint attribute name)
▪ Name of logical device (LDevice attribute inst)
OSI-PSEL, OSI-SSEL, and OSI-TSEL cannot be adjusted.
The SCD file may contain no more than 45 IEDs. It may take several min-
utes to import a complete SCD file. The SCD file should only contain the
IEDs needed.
You can import the CID/SCD file via the Import/Export Manager. To do so,
proceed as follows:
1. Go to
Settings > Import
.
2. Select and import the desired CID/SCD file.