8 Operation
Maschinenfabrik Reinhausen GmbH 2020
178
3587317/21 EN
TAPCON
®
To set the tap position at the maximum analog signal, proceed as follows:
1. Go to
Settings > Analog tap position capture > Pos. at max. analog
signal
.
2. Set the tap position.
3. Press the
Accept
button to save the modified parameter
Pos. at min. analog signal
You can use this parameter to set the tap position of the on-load tap-
changer corresponding to the minimum analog signal (e.g. 4 mA for 4...20
mA signal).
To set the lower tap position, proceed as follows:
1. Go to
Settings > Analog tap position capture > Pos. at min. analog
signal
.
2. Set the tap position.
3. Press the
Accept
button to save the modified parameter
8.17.2.2 Resistor contact series
Carry out the calibration at an ambient temperature that corresponds to nor-
mal operating conditions. This allows you to reduce measurement errors
due to temperature fluctuations.
To capture the tap positions via resistor contact series, you need to perform
a calibration. In order to do this, you have to set the on-load tap-changer's
tap positions corresponding to the maximum and minimum analog signal.
Then you have to carry out on-load tap-change operations across the entire
tap position range. The entire calibration process is performed using wiz-
ards.