15 Technical data
Maschinenfabrik Reinhausen GmbH 2020
317
3587317/21 EN
TAPCON
®
15.5 Analog inputs and outputs
AIO 2
AIO 4
Channels (input or output)
2
4
Inputs
Measuring range
0...10 V
0...20 mA
4...20 mA
Load resistance
(0/4...20 mA)
Max. 300 Ω
Outputs
Signal range
0...10 V
0...20 mA
4...20 mA
Load resistance
(0/4...20 mA)
Max. 500 Ω
Resistor contact series
Maximum resistance 100 Ω...10 kΩ,
max. 35 tap positions
Table 136: Technical data for the AIO 2 and AIO 4 assemblies
Interface
Pin
Description
1
6
11
16
I OUT (+): Current
2
7
12
17
I/U IN (+) U OUT (+): Voltage input
+, current input +, voltage
3
8
13
18
I/U IN (-): Voltage input -, current in-
put -
4
9
14
19
I/U OUT (-): Voltage output -, current
output -
5
10
15
20
Not used
Table 137: Analog inputs and outputs