8 Operation
Maschinenfabrik Reinhausen GmbH 2020
258
3587317/21 EN
TAPCON
®
8.30.1.3.4 NOR
Description
NOR, logical NOT-OR link
Inputs
Input 1…4 (BOOL)
Outputs
Output (BOOL)
Parameter
None
Function
If all configured inputs are FALSE, the output is TRUE,
otherwise it is FALSE.
Initial state
All inputs and outputs are FALSE.
Non-configured inputs are assumed to be FALSE so
that they have no impact on the output.
If no input is configured, the output remains in the initial
state of FALSE anyway.
Table 97: NOR function module
8.30.1.3.5 XOR
Description
XOR, logical EXCLUSIVE-OR link
Inputs
Input 1…2 (BOOL)
Outputs
Output (BOOL)
Parameter
None
Function
If an odd number of inputs is TRUE, the output is
TRUE, otherwise it is FALSE.
Initial state
All inputs and outputs are FALSE.
Non-configured inputs are assumed to be FALSE so
that they have no impact on the output.
If no input is configured, the output therefore remains in
the initial state of FALSE.
Table 98: XOR function module
8.30.1.3.6 NOT
Description
NOT, logical NOT link
Inputs
Input (BOOL)
Outputs
Output (BOOL)
Parameter
None
Function
If the input is TRUE, the output is FALSE, otherwise it
is TRUE.
Initial state
All inputs and outputs are FALSE.
If the input is not configured, it is assumed to be TRUE
so that the output remains in the initial state of FALSE.
Table 99: NOT function module