8 Operation
Maschinenfabrik Reinhausen GmbH 2020
261
3587317/21 EN
TAPCON
®
Function
If there is a rising edge at the Trigger input at any time,
the internal timer is set to zero and starts to run, the
output becomes TRUE.
If the Trigger input becomes FALSE again during the
pulse time, this has no impact on the expiration of the
pulse time.
Once the internal timer has expired, the output be-
comes FALSE.
If the value of Time_ms is less than the cycle time, the
cycle time applies instead.
Initial state
All inputs and outputs are FALSE.
Table 103: Pulse function module
8.30.1.3.11 Symmetrical pulse generator
Description
CLCK, symmetrical pulse generator
Inputs
Enable (BOOL)
Outputs
Output (BOOL)
Parameter
Time ms (UINT32), 1...1,000,000, default = 1,000
Function
The internal timer runs for a long as Enable is TRUE.
When the internal timer has reached or exceeded the
configured time value, the status of the output changes
and the timer is restarted. The configured time there-
fore corresponds to half the period duration of the re-
sulting signal. If the Enable input becomes FALSE, the
output also instantly becomes FALSE and the internal
timer is reset.
If the value of Time_ms is less than the cycle time, the
cycle time applies instead.
Initial state
All inputs and outputs are FALSE.
Table 104: Symmetrical pulse generator function module
8.30.1.3.12 Counter (forwards/backwards)
Description
COUNT, incremental counter
Inputs
Trigger (BOOL)
Direction (BOOL)
Reset (BOOL)
Lock (BOOL)
Outputs
SINT32 (SINT32)
REAL32 (REAL32)
Parameter
Reset value (SINT32), -10,000,000… +10,000,000, de-
fault = 0