![MR TAPCON Скачать руководство пользователя страница 314](http://html.mh-extra.com/html/mr/tapcon/tapcon_operating-instructions-manual_1844346314.webp)
15 Technical data
Maschinenfabrik Reinhausen GmbH 2020
314
3587317/21 EN
TAPCON
®
Interface
Pin
Description
k, k1
Current input for phase L (UI 1) or L1 (UI 3)
l, l1
Current output for phase L (UI 1) or L1 (UI 3)
k2
Current input for phase L2 (UI 3 only)
l2
Current output for phase L2 (UI 3 only)
k3
Current input for phase L3 (UI 3 only)
l3
Current output for phase L3 (UI 3 only)
Table 132: Current measurement
k1
k2
k3
l1
l2
l3
RDY
N
L1
L2
L3
UI 3
55 mm
(2.17 in)
ca. 120 mm
(4.72 in)
1
1
9
m
m
(4
.6
9
i
n
)
54 mm
(2.12 in)
Figure 215: UI 1 und UI 3 dimensions
15.4 Digital inputs and outputs
DIO 28-15
DIO 42-20
DIO 42-20 HL
Inputs (plug-based
electrical isolation)
Quantity
28
42
Logical 0
0...10 V AC (RMS)
0 to 10 V DC
0...40 V AC (RMS)
0 to 40 V DC
Logical 1
18...260 V AC (RMS)
18 to 260 V DC
170...260 V AC (RMS)
170 to 260 V DC
Input current
Typ. 1.3 mA (regardless of
U
)
Simultaneity factor
At 70°C and
U
≥ 230 V: max. 50%
Outputs (floating re-
lay outputs)
Number (number of
change-over contacts in
parentheses)
15 (9)
20 (12)
Contact load capacity
Min.: 5 V, 10 mA
Max. AC: 230 VAC; 5 A
Max. DC: See diagram
Simultaneity factor
Up to 60°C: 100%, > 60°C: -5%/K
Table 133: Technical data for the DIO 28-15 and DIO 42-20 assemblies
Содержание TAPCON
Страница 1: ...Voltage regulator TAPCON Operating Instructions 3587317 21 EN ...
Страница 333: ......